![]() |
![]() |
|
Elements |
![]() |
|
| |
Fully automatic shifting to reserve bank without fluctuating line pressure to the system. |
|
| |
High flow capacity for hospitals or any other medical gas installation. |
|
| |
Weather resistant case protects the internal components. |
|
| |
Easy-to-read LED lights to indicate the status of the manifold. |
|
| |
Audible alarm to indicate when the manifold shifts to the reserve bank of cylinders. |
|
| |
Gas continues to flow if primary power is interrupted; manifold returns to its previous stage when power is restored. |
|
| |
Primary power design accepts 115 |
|
| |
Complies with NFPA 99 requirements. |
|
DiscriptionThe Medical Gas Manifold is fully automatic, including self-shifting
to reserve bank on exhaustion of the service bank without interruption
of gas delivery to the system. The unit complies with the National Fire
Protection Association (NFPA) Specification 99-1999 "Nonflammable
Medical Gas Systems". All critical connections are gas specific,
non-interchangeable, and designed to eliminate gas supply errors. The dual line regulator/single vent 3000 Medical Gas Manifold Control
Unit will include right and left header bars and pigtails for the appropriate
medical gas. Also included for Nitrous Oxide and Carbon Dioxide gases
only are heaters to guard against freezing. The installed system will
automatically switch to the reserve bank when the primary bank is depleted.
When the depleted cylinders are replaced with full cylinders the system
will automatically reset itself in preparation for the next bank change.
The primary side is the bank in use and the remaining side is the bank
on reserve. This designation will automatically change from left to right
and right to left as each bank is depleted and, in turn, refitted with
full gas cylinders. The LED indicator will show a depleted bank by turning red. A buzzer
will also sound to indicate an empty bank or banks. When the system is
reset by replacing the depleted cylinders, the indicator will turn green
and will also silence the buzzer. If the manifold is connected to the
health care facilitys central alarm system, that will also indicate
that the bank was depleted and, in turn, reset. The only manual activity the Medical Gas Manifold requires is the changing
of the depleted cylinders. When a bank is depleted, the Manifold will automatically switch to the
fresh bank, delivering an uninterrupted gas supply to the health care
facility. Changeover is performed by solenoid valves contained in the
control cabinet. In the event of an electrical power failure, both solenoid
valves shall automatically open to provide an uninterrupted gas flow. Under normal operating conditions, the gas will leave the high pressure
cylinders through the pigtails into the header bars. The pigtails have
one-way valves (check valves) to allow the replacement of depleted cylinders
without gas pressure back flow into the remaining depleted cylinders on
that bank. In the event a safety relief device on an individual cylinder
should activate or a pigtail should leak excessively, the local check
valve will also prevent loss of gas from the rest of the cylinders on
that bank. The gas flows through the header bar to the Control Unit. A manually
operated shutoff valve is installed downstream of each header bar. These
valves are located outside the control cabinet, one on the right and one
on the left side. The valves are normally left fully open to allow unrestricted
flow of gas from the two cylinders banks. In case of an emergency, they
can be closed to isolate one or both banks. The gas flows through the manually operated shutoff valve into the primary
regulator. This regulator reduces the high cylinder pressure to an intermediate
pressure. The intermediate pressure gas flows through the solenoid valve
to the line regulator for its final (line) pressure reduction for use
in the health care facility. Two line pressure regulators are installed
in parallel and each is capable of maintaining a constant dynamic delivery
pressure at the maximum designed flow rate of the system. The solenoid valve is the key to the "automatic" mechanism
in the Manifold. This component ensures that the flow of gas is not interrupted
and the pressure does not fluctuate during normal operation. When the
operating bank pressure fails to a pre-determined level, which is controlled
by the preset pressure switches (high and low), the switches will activate
the electronically control board causing the solenoids to switch to the
fresh (reserve) cylinder bank. The Manifold control cabinet has three means of giving continuous information
on the system status. First, pressure gauges to indicate the bank pressures
and the delivery pressure. Second, six indicator LEDs, two green that
indicate which cylinder is in use, two yellow for Reserve Ready and two
red that indicate a bank is now depleted. Third, a loud audible buzzer
gives an alarm when either or both banks are depleted. The six indicators are controlled by sensing the bank pressure. Replacing the depleted cylinders on the empty bank resets the system, changing the indicator from red to yellow. At the same time the yellow LED will change to green to go from Reserve Ready to In Service. LEDs will show red prior to initial pressurization or whenever both cylinder banks are below the preset valve. The manifold is tested for proper operation prior to its shipment. |
||